Permit: T00CM00529

Parcel: 113050430


Addresses:

3502 N OLSEN AV

Inspection Status: Denied

Inspection History: FRAMING

Date Description Inspector Results Comments
08/10/2000 FRAMING Denied IVRS - Inspection 0999*/1. GARAGE IS NOT LOCATED PER PLAN. PLAN CALLS FOR 4'O" TO EASTWALL REVISE PLAN FOR LOCATION AND FIRE RATING OR PROVIDE A SURVEY FO PROPERTY WITH PINS AT EAFCH CORNER. 2. PLAN CALLS FOR 15' X 15' AT NEW GARAGE. ACTUAL 18' X 19'. REVISE PLAN TO AS BUILT AND HAVE APPROVED. 3. SITE PLAN SHOWS ORIGINAL GARAGE 10' X 15'. ACTUAL 12' X 19' REVISE SITE PLAN. 4. UNDERGROUND ELECTRIC CONDUIT TOO SHALLOW MUST BE 18" BELOW GRADE. 5. GARAGE HAS MORE THAN 1 ELECT CIRCUIT MUST HAVE SEPARATE GROUND SYSTEM. INSTALL 2 EAS. 8 FT. GROUND RODS A MINIMUM OF 6' APART CONNECTED TO SUB PANEL W CONTINUOUS #4 WIRE. 6. GARAGE ELECTRIC OUTLETS MUST BE A MINIMUM OF 18" ABOVE FLOOR NOTE FOOTING AND PLATES ARE PER CODE BUT NOT LOCATION FRAMING IS PER CODE.