Permit: T00CM00445

Parcel: 118037500

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
04/10/2000 FRAMING Correction Required ADDTL COMMS - APPROVED - SHEARWALL MODIFICATION AT LAUNDRY WAS INSTRUCTED BY JOHN RIVA FOR FIELD MODIFICATION/REPAIR.
04/07/2000 FRAMING Correction Required ADDTL COMMS - DENIED - 1. PROVIDE ANCHOR BOLTS PER UBC. 2. INISTALL BLOCKING AT WALLS OVER 10HIGH. 3. CRUSHED DUCT. 4. ELECTRIC SWITCH IN THE ATTIC SHALL NOT FACE UP. 5. REVISION NEEDED FOR MISSED BLOCKS. BACK PATIO.
04/07/2000 FRAMING Denied DENIED
04/06/2000 FRAMING Correction Required ADDTL COMMS - DENIED - STOPPED INSPECTION. 1. LAUNDRY SHEAR WALLS 3/6 DETAIL 6/SD3 MUST EXTEND TO BOTTOM CHORD OF SCISSOR TRUSS-NOT TO DEAD WOOD. DETAIL 7. 2. PROVIDE BOTTOM CHORD BRACING AT 6 O.C. FOR TRUSSES A01. 3. A/C CONDENSATE NOT PROPERLY SUPPORTED. REVERSE FLOW. 4. 2X6 IN HALL MUST BEAR ON Lu26 HANGER.
04/06/2000 FRAMING Denied IVRS - Inspection 0999*