Permit: T00CM00426

Parcel: 137117550


Addresses:

1509 W BATHURST RD

Inspection Status: Correction Required

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Date Description Inspector Results Comments
03/21/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - APPROVED - 1. PROVIDE RIDGE BLOCKING PER PLAN. 2. PROVIDE ADDITIONAL DIAGONAL BRACES AT GARAGE ENTRY. 3. ALL TRUSSES ARE OKAY AT THIS TIME.
03/20/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - DENIED - 1. POST TENSION IS NOT PULLED. 2ND INSPECTION WITH SAME RESULTS. 2. ENGINEER SHOULD BE AWARE OF ROOF BEING LOADED PRIOR TO PULLING OF CABLES. PROVIDE ENGINEERS APPROVAL. 3. A RE-INSPECTION FEE WILL BE IMPOSED IF REQUIREMENTS ARE NOT ADDRESSED. 4. HOLD-DOWNS AT REAR ARE NOT NAILED UP.
03/20/2000 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection 0999*
03/10/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - DENIED - STOPPED INSPECTION. 1. HOLD-DOWNS IN FRONT ARE NOT NAILED PER MANUFACTURES SPECS. CANNOT BE NAILED TO TRIMMERS. 2. POST TENSION IS NOT PULLED.
03/10/2000 EXT METAL CLIPS/EXT SHEATHING Denied DENIED
03/07/2000 EXT METAL CLIPS/EXT SHEATHING Correction Required ADDTL COMMS - NOT READY - CANCELLED BY CONTRACTOR.
03/07/2000 EXT METAL CLIPS/EXT SHEATHING Not ready for Inspection NOT READY FOR INSPECTION