Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/25/2001 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK FINAL. |
| 09/24/2001 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 08/28/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLANS STILL DO NOT COMPLETELY REFLECT SYSTEM INSTALLED MOTOR VOLTAGES DIFFERENT, TRANSFORMERS MISSING ON PLANS.2.) NEED TO GROUND TRANSFORMERS AS PER CODE 3.) NEED BONDING DEVICES FROM TRANSFORMER TO 1ST DISCONNECTING MEANS AS PER CODE. |
| 07/26/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) SPLIT BOLT LISTED FOR 2 CONDUTORS ONLY PLEASE INSTALL GROUND BAR AT TRANFER SWITCH. 2.) PLEASE REVISE PLAN THEY DO NOT REFLECT INSTALLED WORK. |
| 04/04/2001 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000* 1) SUPPORT CONDUIT AS PER CODE 2) BOND ENCLOSURE 3) WORK CLEARANCE FOR A/C DISCONNECT 30" X 36" |