Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 05/23/2001 |
BUILDING - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 04/20/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) KITCHEN/BATH GFCI OUTLETS WIRED INCORRECTLY 2) FURNACE/WATER HEATER VENTS MUST EXTEND 1 FOOT ABOVE EVAP COOLER 3) ROMEX IN KITCHEN AT REMOVED WALL INCORRECTLY SPLICED 3 LOCATIONS ALL SPLICES MUST BE MADE IN ACCESSABLE APPROVED ELEC BOXES |
| 04/19/2001 |
BUILDING - FINAL |
|
Denied |
IVRS - Inspection 0999*/1) KITCHEN GFCI OUTLET LEFT ON RANGE WIRED INCORRECTLY (HOT WHEN TRIPPED) 2) BATHROOM GFCI HOT WHEN TRIPPED 3) FURNACE AND WATER HEATER VENTS MUST EXTEND ONE FOOT ABOVE EVAP COOLER 4) ROMEX IN REMOVED WALL BY KITCHEN SPLICED INCORRECTLY IN 3 LOCATIONS ALL SPLICERS MUST BE MADE IN ACCESSABLE APPROVED ELECTRIC BOXES 5) REMOVE ABANDENED GAS LINE IN KITCHEN |