Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00CM00312

Parcel: 10712034A


Addresses:

426 E BLACKLIDGE DR

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
05/23/2001 BUILDING - FINAL Approved IVRS - Inspection 0000*
04/20/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/1) KITCHEN/BATH GFCI OUTLETS WIRED INCORRECTLY 2) FURNACE/WATER HEATER VENTS MUST EXTEND 1 FOOT ABOVE EVAP COOLER 3) ROMEX IN KITCHEN AT REMOVED WALL INCORRECTLY SPLICED 3 LOCATIONS ALL SPLICES MUST BE MADE IN ACCESSABLE APPROVED ELEC BOXES
04/19/2001 BUILDING - FINAL Denied IVRS - Inspection 0999*/1) KITCHEN GFCI OUTLET LEFT ON RANGE WIRED INCORRECTLY (HOT WHEN TRIPPED) 2) BATHROOM GFCI HOT WHEN TRIPPED 3) FURNACE AND WATER HEATER VENTS MUST EXTEND ONE FOOT ABOVE EVAP COOLER 4) ROMEX IN REMOVED WALL BY KITCHEN SPLICED INCORRECTLY IN 3 LOCATIONS ALL SPLICERS MUST BE MADE IN ACCESSABLE APPROVED ELECTRIC BOXES 5) REMOVE ABANDENED GAS LINE IN KITCHEN