Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T00CM00256
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/28/2000 | MECHANICAL - FINAL | Approved | IVRS - Inspection 0000* | |
11/16/2000 | MECHANICAL - FINAL | Denied | IVRS - Inspection 0999* PERMANTLY LABEL EQUIPMENT ON ROOF MARK DATA PLATES ON HEAT PUMPS W/PROPER HEAT KIT INSTALLED AND FUSE UNITS ACCORDINGLY PROVIDE 1" CLEARANCE AROUND "B" VENTS SECONDARY DRAINS MUST DRAIN TO A VISIBLE LOCATION 2 DRAIN LINES INTO ONE PIPE- PIPE MUST BE MIN 1" USE A TEE WHEN TERMINATING CONDENSATE OVER A WASTE VENT ANCHOR CONDENSORS TO CONCRETE PROVIDE A LIGHT AND RECEPTACLE AT AIR HANDLERS IN ATTIC |
|
08/25/2000 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection 0000* OK FOR TEMP C OF O FOR 5 CLASSROOMS OK TO COVER DUCT IN NURSERY ROOM |