Permit: T00CM00256

Parcel: 133201280


Addresses:

602 N WILMOT RD


Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T00CM00256

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2000 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection 0000*
10/03/2000 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection 0245*
MC CABLE TO BE SUPPORTED WITHIN 12" OF J-BOXES AND EVERY 6' AFTER
08/10/2000 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
HALL WAY KIT TO PARISH CENTER
2 1/2" EMTS
2 3/4" EMTS
21" EMTS OK TO COVER
07/19/2000 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection 0000*
CLASSROOMS CEILINGS OK
07/18/2000 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection 0000*