Inspection History: PLUMBING - FINAL
Permit Number - T00CM00181
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/31/2001 | PLUMBING - FINAL | Approved | IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) OK FOR C. OF O. PENDING ANY OTHER INSPECTIONS 3.) MECHANICAL INSPECTOR TO LEAVE UCC FOR GAS. | |
10/30/2001 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION. | |
10/29/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.) YOU STILL HAVE NOT CLEANED OUT THE ROOF DRAINS AND COMPLETED INSTALLATION. 2.) WATER CLOSETS STILL HAVE LESS THAN THE 15" CLEARANCE REQ'D FROM SIDEWALL OR OBSTRUCTION.3.) CHECK ALL COLD WATER PIPING AND ISOLATE COPPER FROM STEEL HANGER OR REPLACE WITH COPPER HANGERS PROVIDE ACCESS TO VIEW ALL OVER HEAD COLD WATER PIPING. | |
10/26/2001 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection 0000*1.) WATER CLOSETS RE-ROUGHED TO 15" FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION OK TO RESET. | |
10/23/2001 | PLUMBING - FINAL | Denied | IVRS - Inspection 0999*1.)PLEASE HAVE YOUR PLUMBING FOREMAN, OR FIELD SUPERITENDANT COMPLETE YOUR PUNCH LIST BEFORE CALLING IN FINAL INSPECTION. 2.) ALL WATER CLOSETS REQUIRE 15" MINIMUM FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION. 3.) HANDICAPPED URINAL ELEVATION 17" AFF MAX 15" FROM CENTER LINE TO SIDE WALL. 4.) GAS VALVE TOO FAR FROM POC ON ROOF TOP UNIT.5.) CLEAN DEBRIS FROM ROD DRAINS AND COMPLETE INSTALLATION. | |
09/11/2001 | PLUMBING - FINAL | Not ready for Inspection | 1.) FINAL CONNECTIONS TO METER OK 2.) OK TO COVER |