Permit: T00CM00181

Parcel: 11708211F


Addresses:

1075 S 10TH AV


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T00CM00181

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2001 PLUMBING - FINAL Approved IVRS - Inspection 0000*1.) ALL CORRECTIONS MADE OK 2.) OK FOR C. OF O. PENDING ANY OTHER INSPECTIONS 3.) MECHANICAL INSPECTOR TO LEAVE UCC FOR GAS.
10/30/2001 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) NOT READY FOR INSPECTION.
10/29/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.) YOU STILL HAVE NOT CLEANED OUT THE ROOF DRAINS AND COMPLETED INSTALLATION. 2.) WATER CLOSETS STILL HAVE LESS THAN THE 15" CLEARANCE REQ'D FROM SIDEWALL OR OBSTRUCTION.3.) CHECK ALL COLD WATER PIPING AND ISOLATE COPPER FROM STEEL HANGER OR REPLACE WITH COPPER HANGERS PROVIDE ACCESS TO VIEW ALL OVER HEAD COLD WATER PIPING.
10/26/2001 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection 0000*1.) WATER CLOSETS RE-ROUGHED TO 15" FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION OK TO RESET.
10/23/2001 PLUMBING - FINAL Denied IVRS - Inspection 0999*1.)PLEASE HAVE YOUR PLUMBING FOREMAN, OR FIELD SUPERITENDANT COMPLETE YOUR PUNCH LIST BEFORE CALLING IN FINAL INSPECTION. 2.) ALL WATER CLOSETS REQUIRE 15" MINIMUM FROM CENTER LINE TO SIDEWALL OR OBSTRUCTION. 3.) HANDICAPPED URINAL ELEVATION 17" AFF MAX 15" FROM CENTER LINE TO SIDE WALL. 4.) GAS VALVE TOO FAR FROM POC ON ROOF TOP UNIT.5.) CLEAN DEBRIS FROM ROD DRAINS AND COMPLETE INSTALLATION.
09/11/2001 PLUMBING - FINAL Not ready for Inspection 1.) FINAL CONNECTIONS TO METER OK 2.) OK TO COVER