Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00CM00181
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/19/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*FOR PERMANENT C OF O. | |
11/13/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*SUBJECT TO INSPECTIONS MAANGER. COMMUNICATION ROOM NO LISTING ON ROOM EVAPORATER UNIT WILL NEED A DISCONNECTING MEANS PER NEC. 430-102 M.C. TERMINATION INTO FC-2 IMPROPER. | |
11/02/2001 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*PARTIAL CALLED OK FOR TEMP C OF O FOR OFFICES. | |
10/29/2001 | ELECTRIC - FINAL | Not ready for Inspection |