Permit: T00CM00134

Parcel: 124172250


Addresses:

1175 E 21ST ST

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
12/13/2000 FRAMING Approved IVRS - Inspection 0000*
11/07/2000 FRAMING Denied IVRS - Inspection 0950*/1. ELECTRIC JUNCTION BOXES MUST BE ACCESSABLE. RELOCATE TO DRYWALL SURFACE. 2. W/H PLATFORM NOT IN 3. MAKE UP ALL GROUNDS IN ELECT BOXES GROUND ALL METAL BOXES. 4. NAIL PROTECT ALL ELECTRIC WIRES WITHIN 1 1/4" OF WALL SURFACE. 5. INCORRECT DRYER EXHAUST DUCT USE 4" ROUND. 5. OVERBUILT AREA OF FRONT GABLE, RAFTERS MUST BE SUPPORTED ON 2 X STRINGERS AT VALLEY. 6. COLLAR TIES REQUIRED ON OVERBUILD RAFTERS AT 4' O.C. 7. LESS TAHN 10 PSI ON GAS GAUGE. 8. YOU MUST PROVIDE 22 X 30 X 30 ATTIC ACCESS. 9. BATHROOM EXHAUST FANS MUST EXHAUST OUTISED NOT IN ATTIC. 10. BATHFANS NOT WIRED. 11. BATHROOM GFCI OUTLETS MUST BE ON DEDICATED 20 AMP CIRCUITS. 12. ELECTRIC OUTLETS REQUIRED WITHIN 6 FT OF DOORS AND EVERY 12 AFTER. 13. OUTSIDE GFCI OUTLETS REQUIRED FRONT AND REAR OF HOUSE. 14. KITHCEN REQUIRES 2 SEPERATE 20 AMP COUNTER. 15. PLAN CALLS FOR RIGID DUCT FLEX USED REUSE PLAN AND HAVE APPROVED BY COT.
10/16/2000 FRAMING Denied IVRS - Inspection 0999*/MUST HAVE ELEC, MECH., PLUMBING AND GAS LINE READY FOR INSPECTIONS ALSO.