Permit: T00CM00021

Inspection Status: Correction Required

Inspection History: FRAMING

Date Description Inspector Results Comments
03/15/2000 FRAMING Correction Required ADDTL COMMS - APPROVED - REINSPECT.
03/13/2000 FRAMING Correction Required ADDTL COMMS - DENIED - STOPPED INSPECTION - TOO MANY ITEMS. 1. CS 16 X 42 STRPAS ARE MISSING AT 2ND FLOOR SHEAR. 2. SUPPORT HORIZONTAL D.W.V. AT 4 O.C. 3. PLUMBING STRAP IS NOT LISTED FOR SUPPORTING D.W.V. USE PROPER SUPPORT. 4. HORIZONTAL WET VENT IS NOT ALLOWED AT SHOWER. 5. TUB/SHOWER IS NOT PROPERLY VENTED. 6. COPPER PLUMBING IS IN CONTACT WITH CONCRETE. MUST BE WRAPPED. 7. NO TRUSS DRAWINGS ON JOB SITE. 8. B GAS VENT WITHIN 1 OF COMBUSTIBLES AT 2ND FLOOR CLOSET.
03/13/2000 FRAMING Denied IVRS - Inspection 0999*