Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2000 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 04/05/2000 |
ELECTRIC - INTERMEDIATE |
|
Correction Required |
ADDTL COMMS - 1. NAIL ROMEX TO WASHER RECEPTACLE 2. NAIL ROMEX TO KITCHEN RECEPTACLE WITHIN 8 IF NO CLAMP ON BOX 3.STRAP ALL WIRING BEFORE ENTERING BACK SIDE OF PANEL (NO HOLDING CLAMP IN PANEL-CONDUCTORS TO BE SUPPORTED) 4. BATH ROOM 2ND FLOOR-EX FAN NOT TIED IN AND LOOSE WIRE IN CEILING 5. 2ND FLOOR HALL CLOSET ROMEX TO RECESSED LT NOT SUPPORTED NOTE-RECHECK ALL ROMEX WIRING SUPPORT-IF CLAMP USED IN BOX STAPLE W/IN 12- NO CLAMP W/IN 8 AND EVERY 4 1/2 |
| 04/05/2000 |
ELECTRIC - INTERMEDIATE |
|
Denied |
DENIED |