Inspection Status: Approved
Inspection History: ELECTRIC - TEMPORARY SERVICE
Permit Number - T00BU02974
Inspection Description - ELECTRIC - TEMPORARY SERVICE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/20/2000 | ELECTRIC - TEMPORARY SERVICE | Approved | PLEASE CLEAR TEMP SERVICE CONTRUCTION | |
10/17/2000 | ELECTRIC - TEMPORARY SERVICE | Denied | IVRS - Inspection 0999* PLEASE OPEN ALL OF TRENCH FOR INSPECTION PLEASE ADD ONE MORE GROUND ROD TO GROUNDING SYSTEM ID TRAILER PANEL BOARDS |
|
10/13/2000 | ELECTRIC - TEMPORARY SERVICE | Partial Approval | WILL NEED A GROUNDING ELECTRODE SYSTEM AT TRAILER PER 250-32 ID FUSE AT MAIN SERVICE FEEDER SER CABLE MUST BE 18" DEEP AND PHYSICAL PROTECTION REQUIRED ABOVE GRADE TO EACH MOBILE UNIT |