Permit: T00BU01823

Parcel: 136402050

Inspection Status: Denied

Inspection History: ELECTRIC - TEMPORARY SERVICE

Permit Number - T00BU01823

Inspection Description - ELECTRIC - TEMPORARY SERVICE

Inspection Status - Denied

Date Description Inspector Results Comments
07/17/2000 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*
CORRECTIONS NOT MADE
07/12/2000 ELECTRIC - TEMPORARY SERVICE Denied IVRS - Inspection 0999*
DRIVE RODS
CONNECT GROUNDING ELECTRODE CONDUCTOR DIRECTLY DO NEUTRAL BUS BAR AND BOND NEUTRAL TO GROUDNING BUS BAR (THIS IS CONSIDERED SERVICE EQUIP IN THIS APPLICATION)
EMT NOT ACCEPTABLE U.G. IMC, RIGID OR SCH 80 PVC IS ACCEPTABLE
ACORN CLAMP WIRE CONNECTION IS TERMINATED WRONG