Permit: T00BU01714


Addresses:

501 E ROGER RD

Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
05/22/2001 POOL/SPA ELECTRIC Approved IVRS - Inspection 0000*ALL GROUNDING IS OK.
05/21/2001 POOL/SPA ELECTRIC Denied IVRS - Inspection 0999*1)USE APPROVED FITTING TO CONNECT TO PULLING ELBOW-CHASE NIPPLES NOT APPROVED.2)VERTIFY EQUIPMENT BOND BACK TO PANEL.3)NEED SUPPORT FOR JUNCTION BOX AND CONDUIT IN AIR.
01/11/2001 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection 0000*
OK BONDING AND POOL PVC
NEED TO SEE UNDERGROUND RUN TO POWER