Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T00BU00759
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2000 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection 0000* OK FINAL S.T.O.I. |
|
09/18/2000 | POOL/SPA ELECTRIC | Denied | IMPROPER SUPPORT AND STRAPPING OF PVC BELOW PANEL RE FEE'S DUE BEFORE NEXT INSPECTION |
|
09/15/2000 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection 0999* color code wire according to code and city ordance support pvc conduit below panel can not install dead front correctly due to bent panel enclosure nneed to see connecion for working clearances |
|
09/08/2000 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection 0999* SECURE MOTOR SWITCH SECURELY CONCENTRIC KNOCK OUT IS LOOSE AND CODE REQUIRES PROPER SUPPORT OF BOXE PVC CONDUIT IS NOT THE PROPER DEPTH THIS PANEL NEEDS TO BE SECURED TO THE MASONARY WALL TIGHTEN SCREW AROUND POOL LIGHT J-BOX SPLICES LOOSE AT POOL LIGHT J-BOX |
|
09/01/2000 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection 0999* COPPER TO ALUMIMUM NEED APPROVED CONNECTIONS POOL EQUIPMENT NOT READY |
|
06/23/2000 | POOL/SPA ELECTRIC | Correction Required | ADDTL COMMS - ALL READY PRE-GUNITE ONLY | |
06/23/2000 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection 0000* | |
06/22/2000 | POOL/SPA ELECTRIC | Correction Required | ADDTL COMMS - OK PREGUNITE ONLY | |
06/22/2000 | POOL/SPA ELECTRIC | Partial Approval | PARTIAL APPROVAL |