Permit: SP-NRP-0425-00211

Parcel: 140374170


Addresses:

7035 S GULL LN

Inspection Status: Re-inspection required

Inspection History: Reconnect Only: Electrical Clearance

Date Description Inspector Results Comments
05/02/2025 Reconnect Only: Electrical Clearance Re-inspection required 05/02/25
1. No GFCI circuits in the kitchen; garbage disposal/ dishwasher outlet.
2. GFCI in downstairs bathroom will not test/reset.
3. K.O. Missing in main service panel.
4. Laundry circuit must be GFCI protected.

154645753
05/14/2025 Reconnect Only: Electrical Clearance Passed Approved for electrical reconnection - RECN Clearance to TEP is required