Inspection Status: Not Ready
Inspection History: ENGR Engineering Final
Permit Number - DP21-0153
Inspection Description - ENGR Engineering Final
Inspection Status - Not Ready
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2022 | ENGR Engineering Final | Not Ready | ||
10/27/2022 | ENGR Engineering Final | Not Ready | ||
07/17/2023 | ENGR Engineering Final | Not Ready | Drainage pipes per Eastern portion of the site have not been inspected during install and backfill. This lack of Inspection will require a Stamped Sealed Certified Letter from the Engineer of Record be provided prior to this final inspection. The Trash Enclosure for this site has not been constructed per the approved Technical Standards section 8-01.9.0 Single Container Enclosure and will need to be removed and replaced correctly. The only other option for keeping the structure as it is what be seek Authorization from Andy Vera with the City of Tucson Environmental Services/General Services. You could ask that he inspect this site and verify whether or not he will allow the Trash Enclosure to remain as it has been Constructed, if so we will need a Document from that Department prior to the Final Inspection. |
|
07/17/2023 | ENGR Engineering Final | Passed | See comments listed on other engineering final. | |
07/25/2023 | ENGR Engineering Final | Passed |