Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Passed
Inspection History: ENGR Grading Final
Permit Number - DP14-0040
Inspection Description - ENGR Grading Final
Inspection Status - Passed
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/23/2017 | ENGR Grading Final | DROBERTS | Approved | Entered by DROBERT5 - |
02/23/2017 | ENGR Grading Final | DROBERTS | Approved | Entered by DROBERT5 - |
02/23/2017 | ENGR Grading Final | DROBERTS | Approved | Entered by DROBERT5 - |
08/05/2016 | ENGR Grading Final | DROBERTS | Continued | Entered by DROBERT5 - LOOKED AT THE SITE AND TRIED TO CONTACT JOEL KRAMER THE E.O.R. AND SEE IF HE IS REPAIRING A REVISED SET OF DRAWINGS FOR THE FINAL CLOSURE OF THE SITE. MANY THINGS HAVE CHANGED ON THIS SITE AND NEED TO BE REFLECTED ON THE REVISED DRAWINGS, I LEFT A MESSAGE FOR JOEL TO CALL ME BACK. |
09/07/2016 | ENGR Grading Final | DROBERTS | Correction Required | Entered by DROBERT5 - MET ONSITE WITH MEMBERS FROM THE CHURCH, JOEL KRAMER E.O.R., AND ARMANDO TOO DISCUSS THE ITEMS THAT ARE INCOMPLETE. CURRENTLY THE WORK THAT IS NEEDED TO COMPLETE THIS SITE FOR ENGINEERING: PROVIDE REVISED DRAWINGS SHOWING ALL THE CHANGES THAT HAVE BEEN MADE TO THE SITE. THIS WILL INCLUDE BUT NOT LIMITED TOO MISSING CURBS, MISSING WALLS(4) AND GATES, MISSING LANDSCAPING MATERIALS(WEST AND SOUTH SIDES OF PROJECT), MISSING BICYCLE PARKING SPACES. 2) CERTIFICATION LETTER FROM THE E.O.R. STATING THAT THE SITE HAS BEEN COMPLETED PER THE APPROVED REVISED DRAWINGS. 3) ROOF DRAINS THAT DRAIN WATER ONTO THE BRICK PAVERS IN THE COMMON AREA BETWEEN THE TWO BUILDING. 4) THE CHANGE FROM ASPHALT TO CONCRETE FOR THE PARKING AREAS. 5) RESOLVE THE ISSUES WITH THE PARKING SPACES AND THE PAALS NOT BEING TO THE PROPER DIMENSIONS. IT APPEARS THAT THE CONCRETE PARKING LOT WAS NOT POURED TO THE PROPER DIMENSIONS OF 60' FROM EDGE TO EDGE. THE CURRENT WIDTH OF THE SITE IS 57 FEET 4 INCHES, THIS CAUSES THE PARKING SPACES TO BE APPROXIMATELY 13 TO 15 INCHES SHORT OF THE REQUIRED LENGTH OF 216 INCHES. |
05/20/2016 | ENGR Grading Final | MRUSSO | Denied | Entered by MRUSSO1 - BUILD THE SITE/GRADING PER THE APPROVED PLANS/OR PROVIDE AND APPROVED PLAN THAT SHOWS WHAT YOU BUILT |
02/23/2017 | ENGR Grading Final | DROBERTS | Approved | Entered by DROBERT5 - |
09/01/2016 | ENGR Grading Final | DROBERTS | Correction Required | Entered by DROBERT5 - CURRENTLY THE WORK THAT IS NEEDED TO COMPLETE THIS SITE FOR ENGINEERING: PROVIDE REVISED DRAWINGS SHOWING ALL THE CHANGES THAT HAVE BEEN MADE TO THE SITE. THIS WILL INCLUDE BUT NOT LIMITED TOO MISSING CURBS, MISSING WALLS(4) AND GATES, MISSING LANDSCAPING MATERIALS(WEST AND SOUTH SIDES OF PROJECT), MISSING BICYCLE PARKING SPACES. 2) CERTIFICATION LETTER FROM THE E.O.R. STATING THAT THE SITE HAS BEEN COMPLETED PER THE APPROVED REVISED DRAWINGS. 3) ROOF DRAINS THAT DRAIN WATER ONTO THE BRICK PAVERS IN THE COMMON AREA BETWEEN THE TWO BUILDING. 4) THE CHANGE FROM ASPHALT TO CONCRETE FOR THE PARKING AREAS. 5) RESOLVE THE ISSUES WITH THE PARKING SPACES AND THE PAALS NOT BEING TO THE PROPER DIMENSIONS. IT APPEARS THAT THE CONCRETE PARKING LOT WAS NOT POURED TO THE PROPER DIMENSIONS OF 60' FROM EDGE TO EDGE. THE CURRENT WIDTH OF THE SITE IS 57 FEET 4 INCHES, THIS CAUSES THE PARKING SPACES TO BE APPROXIMATELY 13 TO 15 INCHES SHORT OF THE REQUIRED LENGTH OF 216 INCHES. |