Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: DP13-0025

Parcel: 121110050


Addresses:

5001 E SPEEDWAY BL

Inspection Status: Complete (Recurring)

Inspection History: ENGR Grading Final

Date Description Inspector Results Comments
09/27/2013 ENGR Grading Final MRUSSO Continued Entered by DROBERT5 - 1) DISCUSSED OPTIONS TO ENSURE COMPLIANCE WITH ADA FOR PARKING AND ACCESS FROM PARKING LOT. 2) ENSURE ROOF DRAINS ARE ROUTED UNDER THE SIDE WALK. 3) PAAL 'S MUST BE 24' FOR TWO WAY TRAVEL 4) INSTALL TRUNCATED DOMES PER APPROVED SITE PLAN
09/27/2013 ENGR Grading Final MRUSSO Continued Entered by DROBERT5 - 1) THE SITE PLAN CALLS OUT EXISTING ADA PARKING AND ACCESS, BUT THERE IS NONE ON SITE. 2) ADA PARKING/LOADING SLOPES MUST BE NO GREATER THAN 2% IN ANY DIRECTION. ADA PEDESTRIAN ACCESS RUN SLOPES MUST BE NO GREATER THAN 5% AND CROSS SLOPE NO GREATER THAN 2% . 3) MAIN ROOF DRAIN MUST NOT DROP ONTO SIDEWALKS PER COT DEV STD