Inspection History Details
Inspection Status: In Violation
Inspection History: COT - ENFC - Code Enforcement - Initial
Case Number - CE-VIO0924-03964
Inspection Description - COT - ENFC - Code Enforcement - Initial
Inspection Status - In Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/08/2025 | COT - ENFC - Code Enforcement - Initial | In Violation | 838 am - Contact w/ tenant on site. 3 outlets in kitchen tested correctly, with grounds. Outlets in living room do not have grounds. Tenant states outlet at west wall of living room (near thermostat) is inoperable. Outlet tests live. Plugged a fan into a known working outlet by front door, it does turn on. Plugged same fan into outlet in question, it does not turn on. Bathroom outlet by sink tests with an open ground. Northwest bedroom outlet on north wall is a 3 prong outlet, tests with hot and ground reversed. SEcond outlet on north wall is loose in wall. Other two outlets are two prong and are live and appear to have no issues. Northeast bedroom has 3 two prong outlets, tested live and appear to have no issues. Issue NOV. -VM |