Parcel: 13508006B


Addresses:

7450 E 22ND ST


Inspection Status: In Violation

Inspection History: COT - ENFC - Code Enforcement - Initial

Case Number - CE-VIO0325-01258

Inspection Description - COT - ENFC - Code Enforcement - Initial

Inspection Status - In Violation

Date Description Inspector Results Comments
03/25/2025 COT - ENFC - Code Enforcement - Initial In Violation Visited the site to assist the case inspectors. Found the electrical new service in violation. Line and load conductors in the same raceways and across meter section(230.7). No bonding(250.92). No grounding electrode system(250..50).
03/27/2025 COT - ENFC - Code Enforcement - Initial In Violation ON SITE WITH INSPECTORS VC & RH, NO ACTIVE ELECTRICAL AT BUILDING #D, MANAGEMENT USING EXTENSION CORD TO FEED ALL UNITS FROM OTHER BUILDINGS, ALSO NEW ELECTRICAL BREAKER BOX, CONDUITS, CABLES AND BREAKERS ALL WITHOUT PROPER PERMIT AND CITY APPROVALS, POSTED STOP WORK ORDER AND CONDEMNED ALL OCCUPIED UNITS AND POSTED DO NOT ENTER SIGNS FOR UNIT 9, 11, 12, 29, 30 &36 ONLEY ONES OCCUPIED THE REST OF THE BUILDING UNIS WERE VACANY ALREADY. TO TEP PLEASE GET CITY CC BEFORE RECONNECT. SEE ATTACHED PICS.