Inspection Status: In Violation
Inspection History: COT - ENFC - Code Enforcement - Initial
Case Number - CE-VIO0124-00060
Inspection Description - COT - ENFC - Code Enforcement - Initial
Inspection Status - In Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2024 | COT - ENFC - Code Enforcement - Initial | In Violation | Unit 107 The living room window is damaged, and the windowpanes are improperly installed not being able to close. Main entrance doorway lacks a threshold and weather strip. Smoke alarms are missing in habitable spaces. The water heater is leaking. Shower tiles have peeled off the rotted wall board. Both bedrooms ceilings and walls have drywall damage from roof water leaks. The kitchen entrance has drywall damage. There are missing electrical receptacle covers in the living room and bedroom. Hallway has an outdoor rated disconnect box that has been installed without a permit in a non-code compliant manner. It’s missing its dead front and the ampacity rating on the breaker. |