Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Parcel: 13508006B

Addresses:


7450 E 22ND ST

Inspection Details

Case Number - CE-VIO0623-04307

Status:
Date Description Inspector Status Comments
COT - ENFC - Code Enforcement - Initial Scheduled ON SITE WITH TFD, COT WATER, MANAGEMENT FOR THE COMPLEX, TENANTS AND INSPECTOR BIGMAN. THERE IS WATER INTRUSION THROUGHOUT UNIT #4 DUE TO A BUSTED PIPE IN THE CEILING OF THE ABOVE UNIT, #24. UNIT #4 SUSTAINED A LARGE AMOUNT OF WATER DAMAGE TO THE INTERIOR CEILING, WALLS, APPLIANCES, MECHANICAL DEVICES, ELECTRICAL DEVICES AND FLOORING. THE ELECTRICAL SYSTEM HAS BEEN COMPROMISED AND A LICENSENED CONTRACTOR SHOULD EVALUATE AND REPAIR THE ELECTRICAL SYSTEM AND DEVICES. THE COMPLEX WORKS OFF OF A MASTER METER FOR THE ELECTRIC SUPPLY. HAVING TEP KILL POWER WOULD HAVE EFFECTED ALL TENANTS AT THE COMPLEX. ALL OF THE INTERIOR BREAKERS IN UNIT #4 WERE TURNED TO THE OFF POSITION. TUCSON WATER TURNED THE WATER OFF TO THE BUILDING AT THE MAIN SHUT OFF. WATER WAS OFF TO ALL UNITS BUT THE PIPE THAT WAS BUSTED IN UNIT 24, CONTINUED TO EXPEL WATER. MANAGEMENT HAD THEIR MAINTENANCE CREW WORKING TO SOLVE THE ISSUES AND MADE THE DECISION TO CONTACT PROFESSIONAL PLUMBERS. DUE TO THE WATER SHUT OFF AT THE MAIN, THE CHILLER SYSTEM WAS NO LONGER COOLING THE UNITS. PERMITS ARE REQUIRED FOR ALL REPAIRS. UNIT #4 IS CONDEMNED AND UNFIT TO OCCUPY. THE UNIT WAS SECURED BY THE RESIDENTS.