Date Description Inspector Status Comments
03/02/2023 COT - ENFC - Code Enforcement - Initial Scheduled VISITED SITE, MET WITH TFD INVESTIGATORS, I WAS INFORMED THAT THERE WAS A SMALL AREA OF THE LIVINGROOM BEING USED FOR SLEEPING AREA THAT HAD BURNED IN THE S/E SECTION OF THE ROOM. INSPECTION BY TFD AND CODE ENFORCEMENT FOUND THAT WIRING COMING FROM A RECEPTICLE ON THE SOUTH WALL AND WIRING COMING FROM THE CEILING HAD COME APART AS THE CASING OF THE WIRE NUTS HAD METED AND THE SPRIAL INTERIOR WAS STILL ON THE ALLUMINUM WIRING FROM THE WALL. THE CONNECTION WAS MISSING A JUNCTION BOX, AND ALL WIRING SIMPLY STUFFED INTO THE RAFTER SPACE. THERE WAS COPPER WIRING TAPED TO THE ALLUMINUM WIRING IN THE CEILING THAT I FEEL ARCHED AND STARTED THE FIRE. BURN MARKS WERE FOUND ON THE ALLUMINUM ROOF SHEATHING. A OUTLET ON THE WEST WALL HAD BEEN ARCHING EVIDENCED BY THE BURN MARKS ON THE COVER PLATE. AND OWNER STATED THERE WERE TWO FUSES, TOP LEFT AND BOTTOM RIGHT, THAT HAD BEEN TRIPPING OR BURNING OUT, AND THAT WAS GOING ON FOR A WHILE. THE 3 RAFTERS IN THE AREA WERE BURNED AND NO LONGER BEARING ON THE EXTERIOR BEARING WALL. (SEE ADDITIONAL NOTES)