Case: T22DV03993
Case Details
Entered Date:
07/14/2022
Applicant:
PRISM HOLDINGS
Description:
AC 150 square feet coverage /553 Square ft over 90 degrees in apartment. AC unit in living room Condo 1 bedroom dwelling
Case Violations
Case Number: T22DV03993
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 1
| Violation Date | Code Statue |
|---|---|
| 07/15/2022 | T.C. Ch. 16, Sec. 16-11(b) (2) COOLING. Every dwelling unit, guest room, and congregate residence shall be provided, in at least one habitable room, with either mechanical cooling or an alternate cooling method. Cooling facilities shall be installed and maintained in a safe condition and in accordance with the manufacturer's recommendations, and shall be capable of providing adequate cooling, appropriate for the climate, to assure a safe living environment. Evaporative cooling shall be maintained to be free of excessive rust, corrosion or mineral deposits that limit proper operation. Any mounting apparatus for a cooling facility must be structurally sound. Mechanical fans or portable evaporative cooling devices may only be used on a temporary basis as the sole source of cooling when the permanent cooling system is being repaired or replaced. |
Outstanding Inspections
Case Number: T22DV03993
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FOLLOW UP CODE ENFORCE | None | Not Inspected |
Completed Inspections
Case Status: COMPLIAN
Case Number: T22DV03993
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2022 | INSP - INITIAL CODE ENFORCMENT | TIDWELL | Approved | ON SITE THE ROOF MOUNTED EVAPORTED COOLER HAS BEEN REMOVED. THE ELECTRICAL JUNCTION BOX AND CONDUIT IS EXPOSED AND NOT PROTECTED. NOT KNOWN IF IT IS ENERGIZED AT THIS TIME. THE WINDOW MOUNTED AIR CONDITION UNIT IS NOT SUFFICIENT FOR THE SIZE OF THE UNIT. THE WINDOW MOUNTED UNIT APPEARS TO BE A 5000 BTU APPLIANCE. THE INTERIOR TEMPATURE READ 92 DEGREES IN THE LIVING WHERE THE WINDOW UNIT IS LOCATED. THE BEDROOM READING WAS 94 DEGREES. IT IS 108 DEGREES OUTSIDE. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T22DV03993
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
| Date | Name |
| 07/14/2022 | CONTACTED BY PHONE |
| 07/15/2022 | CONTACTED BY MAILING |
| 07/15/2022 | NOTICE OF VIOLATION ISSUED |
| 09/06/2022 | VIOLATION CLOSED |