Case Details

Status:

COMPLIAN

Type:

EMERGENCY
Address:

Entered Date:

10/30/2021

Applicant:

29-49 N SCOTT LLC

Description:

BUILDING FIRE

Outstanding Inspections

Case Number: T21DV07676
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
INSP - FOLLOW UP CODE ENFORCE None Not Inspected

Completed Inspections

Case Status: COMPLIAN
Case Number: T21DV07676
Case Description: EMERGENCY
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/01/2021 INSP - INITIAL CODE ENFORCMENT GOODMAN Approved VISITED SITE, MET WITH TFD INVESTIGATORS WHO WALKED ME THRU THE RESTARAUNT TO THE KITCHEN AREA, EXPLAINED THE CAUSE OF THE FIRE WAS A CUTTING BOARD OVERHANGING FORM THE WASH AREA ONTO THE LARGE STOVE THAT WAS OFF BUT THE PILOT MELTING THE CUTTING BOARD AD EVENTUALLY STARTING THE FIRE. I WAS INFORMED THAT THE ANSUL SYSTEM HAD ONLY PARTIALLY DEPLAYED BUT IT WAS ENOUGH TO PUT THE FIRE OUT. I THEN MET WITH S/W GAS TECH WHO JUST CAME DOWN FROM THE ROOF STATING THE HOOD ON THE ROOF TOP WAS IN BAD SHAPE, HAD SOME HOLES IN THE HOOD AND GREASE BUILD UP. MANGER CHIMED IN AND STATED THEIR SERVICE PEOPLE HAVE BEEN OUT SEVERAL TIMES TO MAKE REPAIRS TO THE HOOD BUT THAT THEY HAVE CONTINUED TO HAVE PROBLEMS WITH THE HOOD. MY INSPECTION FOUND THE STOVE TOP WITH MELTED PLASTIC OVER THE RIGHT PORTION OF THE STOVE. I CHECKED THE ANSUL SYSTEM WITH S/W GAS TECH WHO SHOWED ME THAT THE LEFT SIDE OF THE ANSUL SYSTEM DEPLAYED BUT NOT THE RIGHT SIDE BUT ENOUGH TO BUT THE FIRE OUT. I SAW THE PICTURES OF THE DETERIORATED HOOD. I FOUND THE METAL FIRE BARRIER ON THE WALLS HAD BEEN PARTIALLY REMOVED BY TFD LOOKING FOR ADDITIONAL FIRE INSIDE THE WALL. THEIR WAS NO CHARRING TO THE INTERIOR OF THE WALLS BUT METAL WILL NEED TO BE REPLACED. THERE WAS SOME CEILING TILES THAT MAY HAVE BEEN MISSING PRIOR TO THE FIRE OR FIRE DAMAGED BUT NEEDED TO BE REPLACED, AND SURROUNDING WALLS WERE NOT FIRE DAMAGED BUT SMOKE DAMAGED. PIMA COUNTY HEALTH DEPT ARRIVED AND WAS CHECKING COOLERS AND FREEZERS FIRST. ELECTRICAL HAD NOT BEEN AFFECTED AND WAS NOT SHUT OFF. I ASKED PCHD WHAT HIS NOV WOULD INCLUDE SO THAT I COULD DETERMINE A TIME LINE FOR THE STORE TO REOPEN. I DID ISSUE A NOV TO INCLUDE THE ANSUL SYSTEM BE INSPECTED AND REPAIRS MADE, THAT ALL GAS APPLIANCES BE CLEANED, GAS LINES AND CONNECTIONS BE CHECKED FOR LEAKS AND REPAIRED IF NECCESSARY. THAT THE HOOD ON THE ROOF TOP BE REPAIRED OR REPLACED. THAT THE SHEET METAL ON THE WALLS BE REPAIRED OR REPLACED. AND THAT THE CEILING TILES BE REPLACED. A GAS RECONNECT PERMIT WAS INCLUDED IN THE NOV. NOV WAS SIGNED FOR BY THE GENERAL MANAGER OF THE RESTARAUNT. THE REPAIRS AND CLEAN UP REQUIREMENTS WER GONE OVER WITH THE MANAGEMENT SO THEY COULD BETTER UNDERSTAND A TIME FRAME FOR REOPENING. ALL ISSUES WERE ADDRESSED BY C/E AND PCHD. COMPLIANCE / CLOSE CASE.

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T21DV07676
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 1
Date Name
11/01/2021 NOTICE OF VIOLATION ISSUED