Case: T21DV04869
Case Details
Entered Date:
07/30/2021
Applicant:
ZIYAD PROPERTIES LLC ATTN: AMEENA SALTI
Description:
Piñeda’s Tire Shop Has electrical pole possible fire hazard;
Completed Inspections
Case Status: COMPLIAN
Case Number: T21DV04869
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2022 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | ONSITE INSPECTION, THE SERVICE DISCONNECT IS IN A HAZARDOUS STATE, THE BACKER BOARD HAS DETACHED FROM SUPPORT POST. THE SUPPORT POST AND SERVICE HAVE EXCESSIVE MOVEMENT, THE ENTIRE ASSEMBLY IS LEANING AND BEING SUPPORTED BY A TEMPORARY FENCE PANEL WHICH IS WIRE TIED TO A 4 FOOT CHAIN LINK FENCE LOCATED AT THE REAR OF THE PROPERTY. THE SERVICE AND THE SUPPORT SYSTEM ARE UNSAFE AND UNSTABLE. THE POWER WAS ORDERED TO BE DISCONNECTED BY THE CITY OF TUCSON. TUCSON POWER AND ELECTRIC CO DID DISCONNECT POWER FROM THE POLE. . THE ZONING VIOLATIONS FOR THE TIRE BUSINESS WILL BE ADDRESSED WITH A 2022 CASE PENDING SUPERVISOR APPROVAL. |
| 01/28/2022 | INSP - FOLLOW UP CODE ENFORCE | VALDEZ | Approved | ALL DOCS IN ONBASE, CLOSE CASE |
Completed Activity Special Conditions
Case Description - MULTIPLE TYPES
Case Number - T21DV04869
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
| Date | Name |
| 01/22/2022 | CONTACTED BY PHONE |
| 01/22/2022 | CONTACTED IN PERSON |
| 01/22/2022 | CONTACTED BY EMAIL |
| 01/22/2022 | NOTICE AND ORDER ISSUED |
| 01/22/2022 | VIOLATION CLOSED |