Applicant:

KRG TUCSON CORNER LLC

Description:

POWER OUTAGE ELECTRICAL SHORT

Outstanding Inspections

Case Number: T20DV06101
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
INSP - FOLLOW UP CODE ENFORCE None Not Inspected

Completed Inspections

Case Status: COMPLIAN
Case Number: T20DV06101
Case Description: EMERGENCY
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/04/2020 INSP - INITIAL CODE ENFORCMENT VALDEZ Approved THE RESTAURANT JIMMY JOHNS, HAD A WALL OUT ARCING DUE TO THE LOSS OF A 120 V LEG. INTERIOR INSPECTION OF ONE OF THE MAIN DISCONNECTS HAS DETERMINE THAT A 120 V LEG WAS LOSS. WHILE INSPECTING THE MAIN POWER CABINETS AT THE END OF THE BUILDING A HOMELESS PERSONAL BELONGING WERE FOUND INSIDE THE CABINET. TEP WAS CALLED OUT TO INVESTIGATE AND SEE IF THEIR EQUIPMENT WAS TAMPERED WITH. CASCADE ELECTRICAL ONSITE AWAITING TEP RESULTS. MUCH LATER: TEP DID ARRIVE THEY DID TEST THEIR FEEDS INTO THE SERVICE CABINETS WHICH WERE OK, THE BREAKER WAS REMOVED AND CLEANED AND POWER WAS RESTORED. THE ELECTRICIAN DID ALSO RECONNECT THE WALL OUTLET AND ENSURE ALL POWER WAS ON THE THE SUITE. CLOSE CASE

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T20DV06101
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
09/04/2020 CONTACTED BY PHONE
09/04/2020 CONTACTED IN PERSON
09/04/2020 VIOLATION CLOSED

Documents

File Name Document Type  
4356 NOV.PDF DOCUMENTS VIEW