Completed Inspections

Case Status: COMPLIAN
Case Number: T20DV03607
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/24/2020 INSP - INITIAL CODE ENFORCMENT LOPEZ Approved Was called out to by communications to assist Tucson fire, after inspection found that fire started at the back of the property per the fire department, looks like it was an electrical issue by the panel I did find makeshift extension cords being run to the main panel throughout the home, work without permits to the back room, there was also some electrical issues in the interior of the property no face plate at panel, bare wires hanging from outlets, main panel no labeling, double logging this electrical is a fire hazard will be posting unsafe to occupy Until licensed electrician makes repairs to all electrical,
06/30/2020 INSP - FOLLOW UP CODE ENFORCE LOPEZ Approved ALL VIOLATION ABATED WILL BE CLOSING CASE DUETO ALSO PERMIT IN ISSUED STATUS.

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T20DV03607
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
Date Name
05/24/2020 CONTACTED IN PERSON
05/24/2020 NOTICE OF VIOLATION ISSUED