Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING
Address:

Entered Date:

04/22/2019

Applicant:

D & D PENSION PLAN

Description:

water quality is of concern including water leaks

Case Violations

Case Number: T19DV03151
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 7
Violation Date Code Statue
05/01/2019 REFERENCE
05/01/2019 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
05/01/2019 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
05/01/2019 T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions.
05/01/2019 T.C. Ch. 16, Sec. 16-11(f)(1) Every wall or vertical support must be sufficient to carry imposed loads safely, and must not lean, buckle, or split due to defect or lack of maintenance.
05/01/2019 T.C. Ch. 16, Sec. 16-12(b)(3) ROOFS. The roof of every building or structure shall be maintained in a safe condition and shall provide weather protection for that building or structure. Roof coverings shall not be rotted, broken, split, buckled or otherwise deteriorated. T.C. Ch. 16, Sec. 16-12(b) FOUNDATIONS, WALLS, ROOFS, AND CHIMNEYS. Every foundation, wall, roof, chimney and all exterior surfaces of buildings and structures shall be maintained in structurally sound condition and shall provide weather protection. All wood showing evidence of termite damage or decay, where structural or functional integrity is impaired, shall be replaced.
05/01/2019 T.C. Ch. 16, Sec. 16-11(f)(6) All repair work shall be done in a workman like manner.

Outstanding Inspections

Case Number: T19DV03151
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
NPO(EL)-MAIN/PANEL/SUB/DISCONT None Not Inspected
NPO(EL)-WIRING/SWITCH/OUTLT/FX None Not Inspected
NPO(PL)-PLUMBING SYSTEM & FX None Not Inspected
NPO - INSECTS/PESTS None Not Inspected

Completed Inspections

Case Status: COMPLIAN
Case Number: T19DV03151
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/01/2019 INSP - INITIAL CODE ENFORCMENT MENDOZA Approved MAIN ELECTRICAL SERVICE PANEL DOES NOT SHUT PROPERLY, LACKS LABELING, IS MISSING A POP OUT ON THE SIDE AND HAS EXPOSED AND UNSECURED ELECTRICAL ROMEX RUNNING TO THE REAR OF THE STRUCTURE TO THE EAST PORTION OF THE UNIT. EXPOSED ELECTRICAL ON A POLE AT THE FRONT WALL UNSECURED OUTLET IN THE BEDROOM EXTERIOR PLUMBING IS NOT RATED FOR OUTDOOR USE AND IS NOT SECURED. MIXED METAL, PVC AND PEX PATCHES THROUGHOUT THE REAR OF THE STRUCTURE. INSPECTION HOLE AT THE REAR OF THE STRUCTURE IS NOT SECURE. BATHTUB FAUCET IS NOT PROPERLY SEALED AND IS EXPOSED TO THE EXTERIOR OF THE UNIT. BATHROOM SINK LACK PROPER SHUT OFF HANDLE
07/24/2019 INSP - FOLLOW UP CODE ENFORCE MENDOZA Approved ALL PLUMBING WORK COMPLETED BY CONTRACTOR

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T19DV03151
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
Date Name
04/30/2019 CONTACTED BY PHONE
05/01/2019 CONTACTED BY MAILING
05/01/2019 NOTICE OF VIOLATION ISSUED
07/25/2019 VIOLATION CLOSED