Case: T19DV02837
Case Details
Entered Date:
04/11/2019
Applicant:
BRIDEGROOM BRUCE D FAMILY TR
Description:
#2030 E 35TH (DUPLEX) FAULTY ELECTRICITY IN LIVING ROOM-WIFE IN HOSPITAL BED, NOT ABLE TO USE PROPERLY/ WINDOWS DON'T OPEN/ NO FIRE DETECTOR/WROUGHT IRON DOES NOT HAVE INTERIOR UNLOCKING MECHANISM
Case Violations
Case Number: T19DV02837
Case Status: COMPLIAN
Case Description: PROP MAINT MULTIPLE TYPES
Total Violations: 4
| Violation Date | Code Statue |
|---|---|
| 04/19/2019 | T.C. Ch. 16, Sec. 16-11(a)(1) The presence and operations of window openings, size and condition of exits, bars, grills, grates covering windows and openings shall allow for safe and rapid egress in emergency situations. At least one window and all doors in living/sleeping rooms in dwelling units must have an operable release mechanism that allows safe and rapid egress without the use of separate tools. |
| 04/19/2019 | T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson. |
| 04/19/2019 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
| 04/19/2019 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (3) Every habitable room must have at least two electrical receptacle outlets, or one outlet and one electric light fixture. Every bathroom, water closet compartment, and laundry room must have at least one electric light fixture. |
Completed Inspections
Case Status: COMPLIAN
Case Number: T19DV02837
Case Description: PROP MAINT MULTIPLE TYPES
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2019 | INSP - INITIAL CODE ENFORCMENT | MORALES | Approved | ON SITE AT PROPERTY WITH GG. NO DEAD FRONT ON MAIN DISCONNECT. DOUBLE LUGGING ON NEUTRAL. KNOCK OUTS IN BOTTOM OF BOX MISSING FITTINGS. VERIFY ALL CIRCUIT BREAKERS ARE APPROVED AND LISTED FOR APPROVED USE. MULTIPLE BRANCH CIRCUITS HAVE BEEN INSTALLED OUTSIDE WITH OUT PERMITS. NOT CODE COMPLIANCE. MULTIPLE RECEPTACLES INSIDE OF HOME TESTED FOR OPEN GROUND OR ARE INOPERABLE. |
| 06/12/2019 | INSP - FOLLOW UP CODE ENFORCE | MORALES | Approved | ON SITE AT PROPERTY. THE OUTLETS INSIDE ARE NOW WORKING. THE OUTLET OUTSIDE IS NOT WEATHER PROOF. THE SERVICE PANEL HAS NO DEAD FRONT AND IS DOUBLE LUGGING. |
Completed Activity Special Conditions
Case Description - PROP MAINT MULTIPLE TYPES
Case Number - T19DV02837
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
| Date | Name |
| 06/12/2019 | CONTACTED BY PHONE |
| 06/17/2019 | RETURNED MAIL |
| 04/19/2019 | CONTACTED BY MAILING |
| 04/19/2019 | NOTICE OF VIOLATION ISSUED |