Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

08/29/2018

Applicant:

VISTA HERMOSA APARTMENTS LLC

Description:

ELETRICAL ISSUE GIVING SHOCK T PEOPLR WHEN IT RAINS

Completed Inspections

Case Status: COMPLIAN
Case Number: T18DV05225
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/29/2018 INSP - INITIAL CODE ENFORCMENT VIDAL Approved The office called that some getting shocked by the pool. Arrived and the tenants were getting shocked when coming back from the pool. The front door has a metal security door and was feeling a tingle when touching the metal. While on site was able to find a bolt that was securing the metal security door touching a wire. That bolt was removed and all the electrical was working in the unit. Nothing on the metal door. Has issues on the unit and that will be addressed with the maintenance man tomorrow. Will check in 10 days. RV.
06/04/2020 INSP - FOLLOW UP CODE ENFORCE VIDAL Approved Has new tenants and have no complaints at this time on the unit. At this time the case will be closed. Violation Abated, Close Case. RV.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T18DV05225
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
Date Name
06/04/2020 CONTACTED BY PHONE
06/04/2020 VIOLATION CLOSED