Case: T18DV04360
Case Details
Entered Date:
07/27/2018
Applicant:
CITY OF TUCSON
Description:
ELECTRICAL INSPECTION
Outstanding Inspections
Case Number: T18DV04360
Case Status: COMPLIAN
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
INSP - FOLLOW UP CODE ENFORCE | None | Not Inspected |
Completed Inspections
Case Status: COMPLIAN
Case Number: T18DV04360
Case Description: WORK WITHOUT PERMITS-RESIDENTL
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/27/2018 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | HOUSING DEPARTMENT REQUESTED AN INSPECTION ON LARGE GAP BETWEEN THE PANEL COVER ANTHE BREAKERS. THE HUD INSPECTOR FAILED THE UNITS DUE GAP. INSPECTED UNIT 23 BLDG 6 THIS IS A GOULD TYPE PANEL WITH GAPS AT THE BOTTOM CIRCUIT BREAKERS. I BELIEVE THE REASON WHY THERE IS A GAP IS DUE TO THE INTERIOR ENCLOSURE DOES NOT PROTRUDE FAR ENOUGH OUTWARD FROM THE INTERIOR OF THE WALL. IF YOU HAVE A LICENSE ELECTRICIAN TO MAKE THAT ADJUSTMENT IT SHOULD SOLVE THE PROBLEM. NO PANEL SCHEDULE. REPORT WAS EMAILED TO THE HOUSING DEPT.CLOSE CASE |