Case: T17DV02675
Case Details
Entered Date:
06/22/2017
Applicant:
TORINO AVENUE LLC ATTN: MARGEAUX BOWERS
Description:
MAIN ELECTRICAL SERVICE. GROUNDS MAINTENANCE
Case Violations
Case Number: T17DV02675
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Violations: 3
Violation Date | Code Statue |
---|---|
06/22/2017 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
06/22/2017 | T.C. Ch. 16, Sec. 16-12(e) ACCESSORY STRUCTURES. All accessory structures, including but not limited to detached garages, fences and walls, must be structurally sound and free of disrepair. Examples of disrepair include missing slats, posts or blocks, or damage, deterioration or rot. Fences and walls cannot be constructed or covered with materials not designed or commonly used for that purpose, such as pallets and tarps. Fences and walls must be properly anchored so as not to be in danger of failure or collapse. |
06/22/2017 | T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition. |
Outstanding Inspections
Case Number: T17DV02675
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2017 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | MENDOZA | Notice of violation | |
06/23/2017 | NPO(DL)-DILAPIDATED STRUCTURE | MENDOZA | Notice of violation | |
06/23/2017 | NPO - REFUSE/TRASH/DEBRIS | MENDOZA | Notice of violation |
Completed Inspections
Case Status: COMPLIAN
Case Number: T17DV02675
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/14/2017 | INSP - INITIAL CODE ENFORCMENT | MENDOZA | Approved | UNITS 9, 10, 11 ELECTRICAL SERVICE HAS A DISCONNECT BOX BEING UTILIIZED AS A JUNCTION BOX AND NOT RATED AS A JUNTION BOX. WIRING IN THE IN THE DISCONNECT BOX IS UNDERSIZED FOR THE BREAKERS. WIRING FOR ALL THREE UNITS IS RUNNING THROUGH THE SAME CONDUIT. ACCESSORY STRUCTURE ON THE WEST SIDE OF THE PROPERTY IS DILAPIDATED. ACCUMULATION OF TRASH THROUGHOUT THE PROPERTY. |
09/26/2017 | INSP - FOLLOW UP CODE ENFORCE | MENDOZA | Approved | ALL WORK COMPLETED AND APPROVED UNDER PERMIT T17CM05927 |
Completed Activity Special Conditions
Case Description - MULTIPLE TYPES
Case Number - T17DV02675
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date | Name |
06/22/2017 | CONTACTED BY MAILING |
06/22/2017 | NOTICE OF VIOLATION ISSUED |
09/26/2017 | VIOLATION CLOSED |