Case: T17DV00618
Case Details
Entered Date:
02/10/2017
Applicant:
CROWN MEDITERRANEAN LLC
Description:
Unsanitary Conditions (animal feces and trash leakage in hallways)/Building Structural safety(unsafe roof seams/creaking and giving/pipes leaking in walls-possible mold
Case Violations
Case Number: T17DV00618
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 4
Violation Date | Code Statue |
---|---|
03/09/2017 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
03/09/2017 | T.C. Ch. 16, Sec. 16-11(f)(5) All interior coverings, finishes, surfaces including walls, ceilings and floors shall be maintained in a good, clean and sanitary condition. Peeling, chipping, flaking or abraded paint shall be repaired, removed or covered. All walls, ceilings or floors shall be free from holes, breaks and loose or rotting materials. Cracked or loose plaster, wallboard, decayed wood or other defective surface conditions shall be corrected. |
03/09/2017 | T.C. Ch. 16, Sec. 16-12(b)(3) ROOFS. The roof of every building or structure shall be maintained in a safe condition and shall provide weather protection for that building or structure. Roof coverings shall not be rotted, broken, split, buckled or otherwise deteriorated. T.C. Ch. 16, Sec. 16-12(b) FOUNDATIONS, WALLS, ROOFS, AND CHIMNEYS. Every foundation, wall, roof, chimney and all exterior surfaces of buildings and structures shall be maintained in structurally sound condition and shall provide weather protection. All wood showing evidence of termite damage or decay, where structural or functional integrity is impaired, shall be replaced. |
03/09/2017 | T.C. Ch. 16, Sec. 16-13(b) ACCUMULATION OF REFUSE PROHIBITED. Each owner, lessee, tenant, resident or occupant shall maintain a property so it is free of accumulated refuse and debris. Accumulated refuse and debris means contained or uncontained refuse and debris that is present on the property in a manner not authorized by the Tucson Code. Material recycling facilities meeting the requirements of section 15-24.7 are exempt from this prohibition. |
Outstanding Inspections
Case Number: T17DV00618
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 5
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/19/2017 | NPO - INSECTS/PESTS | MENDOZA | Item closed | |
04/19/2017 | NPO - ANIMAL WASTE | MENDOZA | Item closed | |
04/19/2017 | NPO - EXT. BUILDING MAINTENANC | MENDOZA | Item closed | |
05/04/2017 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | MENDOZA | Item closed | |
05/04/2017 | NPO - INT. BUILDING MAINTENANC | MENDOZA | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T17DV00618
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/09/2017 | INSP - INITIAL CODE ENFORCMENT | MENDOZA | Approved | RECCESSED LIGHT ABOVE THE SINK DOES NOT OPERATE. GARBAGE DISPOSAL WIRING IS NOT SECURE. DISPOSAL DOES NOT OPERATE PROPERLY. CENTER HALL LIGHT GLOBE IS MISSING. NORTH BEDROOM CEILING IN THE ROOM AND CLOSET IS BUBBLED. SOUTH BEDROOM SHOWER CEILING REPAIR IS UNFINISHED, MUD ONLY ON THE CEILING, NEEDS SANDING AND PAINTING. HALLWAY REPAIR IS BUBBLED. ANIMAL FECES OUTSIDE SOUTH BEDROOM WINDOW. ROOF TILE MISSING AT THE ELEVATOR ROOM BUILDING 4. ELECTRICAL CONDUIT IS NOT PROPERLY SECURED ON EAST WALL OF ELEVATOR ROOM BUILDING 4 |
05/04/2017 | INSP - FOLLOW UP CODE ENFORCE | MENDOZA | Approved | BATHROOM CEILING COMPLETED. CLOSET CEILING COMPLETED. GARBAGE DISPOSAL WIRING REPAIRED. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T17DV00618
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
Date | Name |
03/07/2017 | CONTACTED BY PHONE |
03/09/2017 | CONTACTED IN PERSON |
04/19/2017 | CONTACTED BY EMAIL |
05/04/2017 | VIOLATION CLOSED |