Case: T15DV09586
Case Details
Entered Date:
12/11/2015
Applicant:
BERGER ARTHUR & JANE CP/RS
Description:
electrical is not working properly in the kitchen
Case Violations
Case Number: T15DV09586
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 1
| Violation Date | Code Statue |
|---|---|
| 12/16/2015 | T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws. |
Outstanding Inspections
Case Number: T15DV09586
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2015 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | STEVENS | Notice of violation | |
| 12/16/2015 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | STEVENS | Initial inspection |
Completed Inspections
Case Status: COMPLIAN
Case Number: T15DV09586
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2015 | INSP - INITIAL CODE ENFORCMENT | STEVENS | Approved | At site, spoke to tenant, Robin. Using an outlet tester, I found that most of the outlets have the hot/neutral reversed. I found two outlets, one in the living room, one in the hallway that had an open ground. The outside outlet wasn't a GFCI. F/U 30 days. |
| 01/22/2016 | INSP - FOLLOW UP CODE ENFORCE | STEVENS | Approved | At site, outlets repaired and replaced. Close case. |
Completed Activity Special Conditions
Case Description - RES: MINIMUM HOUSING
Case Number - T15DV09586
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 4
| Date | Name |
| 12/16/2015 | CONTACTED BY PHONE |
| 12/17/2015 | CONTACTED BY MAILING |
| 12/17/2015 | NOTICE OF VIOLATION ISSUED |
| 01/22/2016 | VIOLATION CLOSED |