Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLIAN

Type:

EMERGENCY
Address:

Entered Date:

08/15/2014

Applicant:

PETERSON EVA ANN & NORTHERN TRUST BANK OF AZ N A TR ATTN: NEAL GERBER & EISENBER

Description:

OLD TOWN ARTISANS FIRE/ ROOF SOUTHEAST CORNER OF COMPLEX COURT/TELLEZ ALARM F142270081 ENGINE 2 REQUESTING (GOODMAN)

Outstanding Inspections

Case Number: T14DV06152
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
08/25/2014 NPO(EL)-MAIN/PANEL/SUB/DISCONT GOODMAN Item closed
08/25/2014 NPO(EL)-WIRING/SWITCH/OUTLT/FX GOODMAN Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T14DV06152
Case Description: EMERGENCY
Total Completed Inspections - 2
End Date Description Inspector Results Comments
08/15/2014 INSP - INITIAL CODE ENFORCMENT GOODMAN Approved VISITED SITE, MET WITH TFD CAPTAIN WHO STATED WHEN THEY ARRIVED THEY DID SEE SMOKE COMING OUT OF THE ROOF VENTS OF TWO DIFFERENT BUILDINGS, VENTS WERE FOR THE SEWER LINES. SPOKE WITH ONE OF THE MAINTANENCE PERSONS WHO STATED HE HEARD A LOUD POP AND THEN FELT THE GROUND SHAKE. MET WITH TEP WHO STATED HE HAD THREE TRANSFORMERS ON THE ELECTRIC POLE AND THE ONE ON THE FAR EAST SIDE HAD TRIPPED. POWER WAS OFFTO THE WEST AND SOUTH SIDES OF THE COURT YARD AREA, POWER THAT FED THE EAST SIDE AND NEW BAR HAD BEEN TURNED OFF AT THE MAINSERVICE PANEL AT THE EAST SIDE OF THE COMPLEX. TEP CALLED FOR A LINE READER WHO STARTED CHECKING THE UNDERGROUND SERVICE LINES. IN THE MEAN TIME I SPOKE WITH THE MAINTANENCE PERSON WHO STATED NEW CLEAN OUTS HAD BEEN ADDED TO THE SEWER LINE ABOUT WHERE HE HAD FELT THE GROUND SHAKE. PLUMBING CONTRACTOR ARRIVED ONSITE. TEP STATED HE LOST A READING AT THE SAME PLACE THE CLEAN OUTS WERE ADDED. PLUMBING CONTRACTOR LOCATED THE SERVICE FEEDS, BUT INSTEAD OF ONE LINE BEING SEVERED DUE TO ARCHING, THERE WERE THREE. ELECTRICAL CONTRACTOR (JOHNNY'S ELECTRIC) ARRIVED ON SITE, SPOKE WITH LEE RAY WHO STATED HE WANTED THE DIRECT BURIAL LINES BROUGHT UP TO CODE MEANING THEY WOULD HAVE TO BE PLACED IN 4 INCH CONDUIT. NOV ISSUED TO OWNER TO REPAIR SEVERED ELECTRICAL FEEDS.
08/26/2014 INSP - FOLLOW UP CODE ENFORCE GOODMAN Approved SPOKE WITH LEERAY HANLEY, IT WAS DETERMINED THAT THE BREAK IN THE POWER LINES OCCURRED ON THE TEP SIDE OF THE PROPERTY, THEREFORE TEP OK'ED THE USE OF A TEMPORARY UNDERGROWUND SPLICE, WAS INSPECTED BY BOTH LEE RAY AND TEP AND APPROVED. THEREFORE A PERMIT WAS NOT REQUIRED AND PERMIT #T14CM05348 WAS WITHDRAWN. EMAIL WAS SENT TO BOTH MIKE WYNEKEN AND MYSELF, SEE EMAIL IN CASE PACKET. POWER HAS BEEN RESTORED. COMPLIANCE / CLOSE CASE

Completed Activity Special Conditions

Case Description - EMERGENCY
Case Number - T14DV06152
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 1
Date Name
09/18/2014 VIOLATION CLOSED

Documents

File Name Document Type  
NOV-06152.PDF DOCUMENTS VIEW