Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case Details

Status:

COMPLIAN

Type:

FIRE AT COMMERCIAL BUILDING

Entered Date:

07/18/2014

Applicant:

CAMPBELL PLAZA ONE LLC

Description:

F14199098 - HOOD FIRE (FIVE GUYS)

Completed Inspections

Case Status: COMPLIAN
Case Number: T14DV05005
Case Description: FIRE AT COMMERCIAL BUILDING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
07/18/2014 INSP - INITIAL CODE ENFORCMENT VINDIOLA Approved 07/18/14 ARRIVED ON SITE WITH TFD THERE // ALL UTILITIES ON WATER, GAS AND ELECTRICITY// FIRE WAS IN HOOD SYSTEM AND WAS A WIRE TO HEATING ELEMENT THAT SHORT CIRCUITED AND BEGAN TO SMOKE NO FIRE // BILL FROM CONSTRUCTION CREW DISCONNETED HEATING ELEMENT FROM JUNCTION BOX ON ROOF AND PULLED HEATING ELEMENT OUT OF SYSTEM WHICH IS NOT NEEDED IN SUMMER TIME ONLY IN WINTER // CIRCUIT WAS PROPERLY DISCONNECTED IN JUNCTION BOX // NOV GIVEN ON SITE FOR MAINT ON MECHANICAL DEGREASE SYSTEM ON ROOF AND ELECTICAL FOR PLACING RUBBER GASKET IN JUCTION BOX ON ROOF AND SUPPORT POWER CABLE SO THAT IT DOES NOT SIT ON ROOF AND SPACING FROM COPPER DRAIN PIPE // SIGNED BY OWNER ON SITE AND MANAGER AND I EXCHANGED CONTACT INFO // WILL F/U IN 48 HRS // AV
08/07/2014 INSP - FOLLOW UP CODE ENFORCE VINDIOLA Approved 08/07/14 BACK ON SITE TO FIND NEW LINE INSTALLED // ROOF CLEAN UP // CORD OFF THE SURFACE OF ROOF // NEW RUBBER BUSHING ON JUNCTION BOX // WILL MOVE TO CLOSE OUT THIS CASE // AV

Completed Activity Special Conditions

Case Description - FIRE AT COMMERCIAL BUILDING
Case Number - T14DV05005
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
Date Name
07/21/2014 CONTACTED BY PHONE
07/21/2014 NOTICE OF VIOLATION ISSUED
12/15/2014 VIOLATION CLOSED
07/21/2014 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (3) Every habitable room must have at least two electrical receptacle outlets, or one outlet and one electric light fixture. Every bathroom, water closet compartment, and laundry room must have at least one electric light fixture.
07/21/2014 T.C. Ch. 16, Sec. 16-11(d) MECHANICAL EQUIPMENT. All mechanical equipment and appliances shall be properly installed, maintained in a safe, working, operating condition, and shall be free of any defect that impairs operability.

Documents

File Name Document Type  
DSCN4996.JPG IMAGES VIEW
DSCN4997.JPG IMAGES VIEW
DSCN5002.JPG IMAGES VIEW
DSCN5004.JPG IMAGES VIEW
DSCN5011.JPG IMAGES VIEW
DSCN5014.JPG IMAGES VIEW