Case: T14DV02628
Case Details
Entered Date:
04/24/2014
Applicant:
CHAPEL AVENUE LLC
Description:
Breakers keep tripping. Owner re-routed from one panel box to another. Tenant called TEP. Techincian stated they call an electrcian, 2-100 amp breakers? house not grounded. Possible broke floor joist in living room.
Case Violations
Case Number: T14DV02628
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Violations: 1
| Violation Date | Code Statue |
|---|---|
| 04/30/2014 | T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe. |
Outstanding Inspections
Case Number: T14DV02628
Case Status: COMPLIAN
Case Description: MULTIPLE TYPES
Total Outstanding Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/26/2014 | NPO(EL)-MAIN/PANEL/SUB/DISCONT | MMENDOZA | Item closed | |
| 06/26/2014 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | MMENDOZA | Item closed |
Completed Inspections
Case Status: COMPLIAN
Case Number: T14DV02628
Case Description: MULTIPLE TYPES
Total Completed Inspections - 2
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/29/2014 | INSP - INITIAL CODE ENFORCMENT | MMENDOZA | Approved | Checked electrical service and found 1- 100amp all in one panels on unit. found 100amp all in one panel dead at the meter,and back fed to an interior sub panel , then to the 100amp main panel |
| 06/26/2014 | INSP - FOLLOW UP CODE ENFORCE | MMENDOZA | Approved | 06/26/2014 11:52am Researched Property Research Online ,Under permit #T14EL00079 ( replace sub panel like for like ) Visited property to verify and confirm all work has been completed. VIOLATION ABATED ,close case. |
Completed Activity Special Conditions
Case Description - MULTIPLE TYPES
Case Number - T14DV02628
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 5
| Date | Name |
| 04/28/2014 | CONTACTED BY PHONE |
| 05/12/2014 | CONTACTED IN PERSON |
| 05/01/2014 | CONTACTED BY MAILING |
| 05/01/2014 | NOTICE OF VIOLATION ISSUED |
| 07/09/2014 | VIOLATION CLOSED |