Case: T14DV01415
Case Details
Entered Date:
03/11/2014
Applicant:
TOP GUN REALTY. ATTN; LAUREN KRING
Description:
CUT POWER FROM THE POLE
Outstanding Inspections
Case Number: T14DV01415
Case Status: COMPLIAN
Case Description: EMERGENCY
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FOLLOW UP CODE ENFORCE | None | Not Inspected | ||
| NPO(EL)-MAIN/PANEL/SUB/DISCONT | None | Not Inspected | ||
| 03/11/2014 | NPO(EL)-WIRING/SWITCH/OUTLT/FX | VALDEZ | Item initialized |
Completed Inspections
Case Status: COMPLIAN
Case Number: T14DV01415
Case Description: EMERGENCY
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/06/2014 | INSP - INITIAL CODE ENFORCMENT | VALDEZ | Approved | THE MAIN DISCONNECT HAS DETACHED ITS SELF FROM THE BUILDING DUE TO THE FAILURE OF THE ANCHORS. THE ENTIRE DISCONNECT WAS BEING HELD UP BY THE RISER CLAMPS AND THE EMT CONDUIT. THE METER WAS ENERGIZED. THE HOME WAS VACANT. THE CONCERN WAS IF THE SYSTEM COLLAPSES THE SERVICE ENTRANCE CONDUCTORS WOULD FALL ON BORDERING PROPERTIES WHICH ARE OCCUPIED. WILL HAVE TEP CUT POWER AT THE POLE. CLOSE CASE |
Completed Activity Special Conditions
Case Description - EMERGENCY
Case Number - T14DV01415
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 2
| Date | Name |
| 03/11/2014 | CONTACTED BY PHONE |
| 03/11/2014 | VIOLATION CLOSED |