Case Details

Status:

COMPLIAN

Type:

RESIDENTIAL FIRE
Address:

Entered Date:

06/03/2013

Applicant:

RAMIREZ ALFREDO & ROSA E CP/RS

Description:

HAD A HOUSE FIRE NEXT DOOR AND DID DAMAGE TO THE HOUSE FROM THE HEAT

Case Violations

Case Number: T13DV03775
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Violations: 1
Violation Date Code Statue
06/03/2013 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.

Outstanding Inspections

Case Number: T13DV03775
Case Status: COMPLIAN
Case Description: RESIDENTIAL FIRE
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/26/2013 NPO(EL)-MAIN/PANEL/SUB/DISCONT RVIDAL Follow-up inspection
09/26/2013 NPO(EL)-WIRING/SWITCH/OUTLT/FX RVIDAL Follow-up inspection
09/26/2013 NPO(HC)-COOLING RVIDAL Follow-up inspection
09/26/2013 NPO(HC)-HEATING & VENTILATION RVIDAL Follow-up inspection

Completed Inspections

Case Status: COMPLIAN
Case Number: T13DV03775
Case Description: RESIDENTIAL FIRE
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/30/2013 INSP - INITIAL CODE ENFORCMENT RVIDAL Approved Had a fire next door and did damage to the electrical meter and T.E.P. had it changed. The electrical main disconnect has triple lugging on the feed side and not able to remove power due to on the line side and above the fuses. The triple lugging are from an AC and dryer being added and not having breakers. The go to boxes added to the disconnect and are on the outside of the main disconnect. The cable dish is worped from the heat along with the cables and the cable box mounted on the red brick wall. The AC package unit on the roof has the smell of smoke going into the house and will need to be checked for damage due to heat on the unit. The beam end on the front porch has some burning and only on the end cut. The olylanders were burned near the fence near the neighbors property that burned. Will do N.O.V. for the electrical and will send by mail.
09/26/2013 INSP - FOLLOW UP CODE ENFORCE RVIDAL Approved The permit has been finaled on 9-25-13 and at this time the case will be closed. Violation Abated, Close Case. RV.

Completed Activity Special Conditions

Case Description - RESIDENTIAL FIRE
Case Number - T13DV03775
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 3
Date Name
06/24/2013 CONTACTED BY MAILING
06/24/2013 NOTICE OF VIOLATION ISSUED
10/02/2013 VIOLATION CLOSED

Documents

File Name Document Type  
NOV T13DV03775 6-4-13.PDF DOCUMENTS VIEW