Heat is not working

Case Violations

Case Number: T12DV11333
Case Status: REFERRED
Case Description: RES: MINIMUM HOUSING
Total Violations: 5
Violation Date Code Statue
01/08/2013 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
01/08/2013 T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson.
01/08/2013 T.C. Ch. 16, Sec. 16-11(b) (1) HEATING. Every habitable room within a dwelling unit, guest room, and congregate residence shall be provided with safe heating facilities which are properly installed and maintained in a sound condition and are capable of providing adequate heating, appropriate for the climate, to assure a safe living environment. All heating facilities shall be free from health hazards associated with ventilation, mounting, electrical and gas connections and other defects. Unvented fuel-burning heaters must be of a listed and approved type, and are prohibited as the sole source of heating. Ovens, stoves or ranges, or other cooking appliances cannot be used for the purpose of heating any portion of a dwelling. Listed, portable space heaters may only be used as the sole source of heating on a temporary basis when the permanent heating system is being repaired or replaced.
01/08/2013 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
01/08/2013 T.C. Ch. 16, Sec. 16-11(d) MECHANICAL EQUIPMENT. All mechanical equipment and appliances shall be properly installed, maintained in a safe, working, operating condition, and shall be free of any defect that impairs operability.

Outstanding Inspections

Case Number: T12DV11333
Case Status: REFERRED
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
06/19/2014 NPO(EL)-MAIN/PANEL/SUB/DISCONT VIDAL Item closed
06/19/2014 NPO(EL)-WIRING/SWITCH/OUTLT/FX VIDAL Item closed
06/19/2014 NPO(PL)-GAS SUPPLY/CONNECT VIDAL Item closed
06/19/2014 NPO(PL)-WATER HEATERS VIDAL Item closed
06/19/2014 NPO - SMOKE ALARMS VIDAL Item closed
06/19/2014 NPO - EXT. BUILDING MAINTENANC VIDAL Item closed
06/19/2014 NPO - WORK WITHOUT PERMIT VIDAL Item closed
06/19/2014 NPO - INT. BUILDING MAINTENANC VIDAL Item closed
12/28/2012 NPO(HC)-HEATING & VENTILATION JREED Item initialized

Completed Inspections

Case Status: REFERRED
Case Number: T12DV11333
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
01/03/2013 INSP - INITIAL CODE ENFORCMENT RVIDAL Approved Met with the tenant and did an inspection on the property. Found where the forced air furnace has been removed from the house and is standing on the front yard. The heat exchangers are cracked or split at the top. I did check for other items and found lacking smoke detectors in all the bedrooms and the one inplace in the hallway is not working. Found water heater in a storage room that has no vents to the exterior for combustion relief. The back room appears to have been added and will check records. The front porch and the carport need to be checked for a permit due to the setbacks and over-spanding of the rafters. RV.
06/19/2014 INSP - FOLLOW UP CODE ENFORCE VIDAL Approved This case has been referred to T14DV00015 for a fire call and still has the same issues. Will address the issues on the other case. Close Case. RV.

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T12DV11333
Case Status: REFERRED
Total Completed Case Activity Conditions: 5
Date Name
02/05/2013 CONTACTED BY PHONE
01/16/2013 CONTACTED IN PERSON
01/16/2013 NOTICE AND ORDER ISSUED
02/05/2013 PERMIT ISSUED - T##XX#####
01/03/2013 RESEARCH