Case Details

Status:

COMPLIAN

Type:

RES: MINIMUM HOUSING

Entered Date:

04/16/2012

Applicant:

MARIA ELVA MOROYOQUI

Description:

SW GAS LOCKED HEATER SINCE DEC, OUTLETS NOT GFI.....

Case Violations

Case Number: T12DV02959
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Violations: 3
Violation Date Code Statue
05/09/2012 T.C. Ch. 16, Sec. 16-11(c) ELECTRICAL SYSTEM. (1) All dwellings and dwelling units shall be provided with electrical service. Electrical facilities connected to or in any building or structure are to be maintained hazard-free and in a state of good repair. The electrical system shall be free from such hazards as bare wiring; overloaded circuits or services; equipment not properly grounded; over-fused circuits; misuse of wiring, including the use of extension cords in lieu of permanent wiring; non-approved wiring; and wiring exposed to moisture or extreme heat. Broken, loose, frayed, inoperable, defective or missing portions of the electrical service, lines, switches, outlets, fixtures and fixture coverings shall be repaired or replaced. (2) All electrical equipment, wiring and appliances shall be installed and maintained in a safe manner and in accordance with all applicable laws.
05/09/2012 T.C. Ch. 16, Sec. 16-4. PERMITS REQUIRED. Unless otherwise exempt pursuant to section 301 of the Administrative Code, as adopted by reference per section 6-1 of this Code, or pursuant to any other ordinance or statute, no building, structure or building service equipment regulated by this chapter or by the technical codes adopted by the city shall be built, erected, constructed, enlarged, altered, repaired, moved, improved, removed, converted or demolished unless a permit first has been obtained from the building official in the manner provided in the administrative and building codes adopted by the city. The purpose of a permit is to ensure that all construction is inspected by qualified City of Tucson personnel as directed by ordinance to verify compliance with city codes. Failure to obtain proper permit with inspections and approvals shall deem the construction to be unsafe.
05/09/2012 T.C. Ch. 16, Sec. 16-11(f)(5) All interior coverings, finishes, surfaces including walls, ceilings and floors shall be maintained in a good, clean and sanitary condition. Peeling, chipping, flaking or abraded paint shall be repaired, removed or covered. All walls, ceilings or floors shall be free from holes, breaks and loose or rotting materials. Cracked or loose plaster, wallboard, decayed wood or other defective surface conditions shall be corrected.

Outstanding Inspections

Case Number: T12DV02959
Case Status: COMPLIAN
Case Description: RES: MINIMUM HOUSING
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
10/02/2012 NPO(EL)-WIRING/SWITCH/OUTLT/FX LPUMPHRE Item closed
10/02/2012 NPO(PL)-PLUMBING SYSTEM & FX LPUMPHRE Item closed
10/02/2012 NPO(HC)-HEATING & VENTILATION LPUMPHRE Item closed
10/02/2012 NPO - SMOKE ALARMS LPUMPHRE Item closed
10/02/2012 NPO - INT. BUILDING MAINTENANC LPUMPHRE Item closed

Completed Inspections

Case Status: COMPLIAN
Case Number: T12DV02959
Case Description: RES: MINIMUM HOUSING
Total Completed Inspections - 2
End Date Description Inspector Results Comments
05/03/2012 INSP - INITIAL CODE ENFORCMENT LPUMPHRE Approved On site inspection at request of tenant who had list of complaints for review by code enforcement. Violations found: lack of operable fire detector in hallway outside bedrooms, section of wall in hallway lacking drywall (open to framing); gas heater turned off by SWG due to hazardous conditions (ventilation, etc.), ventilation for heater is not installed properly. Master bath shower and fixtures are not installed properly and are non operational. Kitchen sink is loose, rending plumbing susceptible to damage. Two electrical outlets in kitchen prep area require GFCI outlets. See research for additional information.
09/26/2012 INSP - FOLLOW UP CODE ENFORCE LPUMPHRE Approved Violations abated; met owner at property. The heater ventilation appeared to be installed correctly at time of inspection from interior viewpoint only; determined that permit not required. It has been noted that SW gas was out 9/21/12, but wasn't able to access interior or assess condition of ventilation themselves. Owner was advised to have SW gas come back out to be able to check appliances before use per visit. Apparently they left meter on 9/21/12.

Outstanding Case Activity Conditions

Date Name Approved
05/09/2012 T.C. Ch. 16, Sec. 16-11(a)(3) Every existing dwelling unit shall be provided with smoke detectors in good operating condition as required by the Tucson Fire Code of the City of Tucson. Not Approved
05/09/2012 T.C. Ch. 16, Sec. 16-11(b) (1) HEATING. Every habitable room within a dwelling unit, guest room, and congregate residence shall be provided with safe heating facilities which are properly installed and maintained in a sound condition and are capable of providing adequate heating, appropriate for the climate, to assure a safe living environment. All heating facilities shall be free from health hazards associated with ventilation, mounting, electrical and gas connections and other defects. Unvented fuel-burning heaters must be of a listed and approved type, and are prohibited as the sole source of heating. Ovens, stoves or ranges, or other cooking appliances cannot be used for the purpose of heating any portion of a dwelling. Listed, portable space heaters may only be used as the sole source of heating on a temporary basis when the permanent heating system is being repaired or replaced. Not Approved
05/09/2012 T.C. Ch. 16, Sec. 16-11(e) PLUMBING SYSTEMS. (3) All plumbing systems are to be maintained safe and hazard free and in a state of good repair. Every dwelling or dwelling unit shall have an adequate potable water supply. Every plumbing fixture, water and waste-pipe, and gas connection shall be properly installed in accordance with all applicable laws and maintained in good and sanitary working condition so as to prevent structural deterioration or health hazards, and are to be free from leaks and obstructions. Not Approved

Completed Activity Special Conditions

Case Description - RES: MINIMUM HOUSING
Case Number - T12DV02959
Case Status: COMPLIAN
Total Completed Case Activity Conditions: 10
Date Name
04/23/2012 CONTACTED BY PHONE
05/11/2012 CONTACTED IN PERSON
08/23/2012 CONTACTED BY MAILING
08/30/2012 CERTIFIED RECEIPT CARD
05/09/2012 NOTICE OF VIOLATION ISSUED
08/23/2012 CITATION ISSUED
10/17/2012 VIOLATION CLOSED
08/23/2012 COURT HEARING INFO
05/09/2012 RESEARCH
07/11/2012 REINSPECTION FEE - FIRST