Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

05/24/2011

Applicant:

26 PALMS DELAWARE LLC & SIERRA INDUSTRIAL

Description:

Sprinkler Deficiencies

Outstanding Inspections

Case Number: T11FR01005
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
INSP - REINSPECTION None Not Inspected
05/23/2011 VIOL - FIRE PROTECTION SYSTEMS CSCHULTZ Correction Required 1. Riser # 1 (east) the bottom gauge port is plugged. Shall repair 2. Pressure gauges are outdated - Shall recalibrate or replace gauges. 3. The 6" Kennedy riser control valve will not close. - Shall repair or replace valve. 4. Shall have a 5 year check valve inspection done. 5. Shall have a sprinkler inspection done on properties.