Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T11FR00970
Case Details
Entered Date:
05/04/2011
Applicant:
SAFEWAY INC
Description:
FPI generated by hood system deficiency report, Wildcat, 39927, 10/7/10, T11FR00582 Dennis Lindeman, 514-2008, Building Representative
Outstanding Inspections
Case Number: T11FR00970
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2011 | INSP - FULL | dgreenl1 | Violation | Repair deficiencies as noted in hood system report from Wildcat fire dated 10/7/10 - System 1 (Deli): TFC 904.11.2 - System interconnection. The actuation of the fire suppression system shall automatically shut down the fuel or electrical power supply to the cooking equipment. The fuel and electrical supply reset shall be manual. _____ Exhaust fan shut off TFC 904.3.5 - Monitoring. Where a building fire alarm system is installed, automatic fire-extinguishing systems shall be monitored by the building fire alarm system in accordance with NFPA 72. _____ Building alarm system activation TFC 107.1 - Maintenance of safeguards. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection, or any other feature is required for compliance with the provisions of this code, or otherwise installed, such device, equipment, system, condition, arrangement, level of protection, or other feature shall thereafter be continuously maintained in accordance with this code and applicable referenced standards. Exit Sign Illumination: _____ Back door _____ Stock area hall _____ West front door _____ Test and repair (as needed) EXIT signs for main sales floor exits. _____ Repair/replace broken EXIT sign stock area hallway Repair Emergency Light: _____ Break room _____ Stock room _____ Stock area _____ Stock area hall _____ West front door _____ Pillar, west by produce Test (and repair as needed) lights above main sales floor. TFC 901.6 - Inspection, testing and maintenance. Fire … extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective _____ Replace escutcheon in break room mop closet. TFC 605.4 - Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove un-protected power tap, deli soda table TFC 703.1 - Maintenance The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Replace missing and damaged ceiling tiles: _____ Bakery storage _____ Computer room TFC 605.3 - Working space and clearance. A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area around electrical panels and transformers. TFC 315.2.3 - Equipment rooms. Combustible material shall not be stored in boiler rooms, mechanical rooms or electrical equipment rooms. _____ Remove storage from electrical service room. TFC 605.1 - Abatement of electrical hazards. Identified electrical hazards shall be abated. _____ Repair outlet behind claw game beside West door. TFC 508.5.4 - Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____ Clear area around FDC (Sprinkler hook-up) behind store. |