Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T11FR00940
Case Details
Entered Date:
04/27/2011
Applicant:
MUELLER JON W & PATRICIA E JTRS/CPRS
Description:
Mueller Mfg. 4/25/11 Jon Mueller 520-622-6115
Outstanding Inspections
Case Number: T11FR00940
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/28/2011 | VIOL - MEANS OF EGRESS | MPursley | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the drop bars from exit doors 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your side exit |
04/28/2011 | VIOL - FLAMMABLE FINISHES | MPursley | Correction Required | IFC Chapter 15:Flammable Finishes _____Spray booth must be in compliance with ch. 15 for spraying of flammable finishes. or _____Convert to water based finishes. or _____Cease and desist use of spray booth. |
04/28/2011 | VIOL - FLAMMABLE LIQUIDS | MPursley | Correction Required | 3404.3.3.3 Clear means of egress. Storage of flammable liquids shall not be stored within 10' of exit. _____Move flammable liquids cabinet from exit pathway. |
Completed Inspections
Case Status: FIELD
Case Number: T11FR00940
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/30/2011 | INSP - REINSPECTION | MPursley | Approved | I visited the site with Capt. Langejans and Chief Baker. After review, the Chief gave untill May 31 to transition to water base finishes, stop work, or come in to spray booth compliance. All corrections made and transitioned to water base finishes 6/27/11 |