Outstanding Inspections

Case Number: T11FR00940
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date Description Inspector Results Comments
04/28/2011 VIOL - MEANS OF EGRESS MPursley Correction Required 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the drop bars from exit doors 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ Remove all obstructions and be sure to always maintain a clear and obstruction free path to your side exit
04/28/2011 VIOL - FLAMMABLE FINISHES MPursley Correction Required IFC Chapter 15:Flammable Finishes _____Spray booth must be in compliance with ch. 15 for spraying of flammable finishes. or _____Convert to water based finishes. or _____Cease and desist use of spray booth.
04/28/2011 VIOL - FLAMMABLE LIQUIDS MPursley Correction Required 3404.3.3.3 Clear means of egress. Storage of flammable liquids shall not be stored within 10' of exit. _____Move flammable liquids cabinet from exit pathway.

Completed Inspections

Case Status: FIELD
Case Number: T11FR00940
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/30/2011 INSP - REINSPECTION MPursley Approved I visited the site with Capt. Langejans and Chief Baker. After review, the Chief gave untill May 31 to transition to water base finishes, stop work, or come in to spray booth compliance. All corrections made and transitioned to water base finishes 6/27/11