Case: T11FR00923
Case Details
Entered Date:
04/26/2011
Applicant:
LAUREMAR INC
Description:
6" gap in filters needs filled exhaust for shut down with system activation and needs to stay on
Outstanding Inspections
Case Number: T11FR00923
Case Status: FIELD
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2011 | INSP - FULL | ALOPEZ | Correction Required | 6" gap in filters needs filled exhaust fan shut down with system activation and needs to stay on |
05/25/2011 | VIOL - FIRE PROTECTION SYSTEMS | MPursley | Correction Required | Called on 5/5 and they said that every thing was done and they would send report. I recieved the report on 5/9 and it was the same as I had. I visited on 5/23 and found all filters in place, it looked like an older system so they are checking when it was installed and getting back to me for the fan shut off. |
Completed Inspections
Case Status: FIELD
Case Number: T11FR00923
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2011 | INSP - REINSPECTION | MPursley | Approved | All panels in place 5/23/11 on RI System as built, no action required for exhaust fans. |