Case: T11FR00900
Case Details
Entered Date:
04/25/2011
Applicant:
DOSS LIVING TRUST
Description:
Moving Services Inc. 3/25/11 Anny/Josh Shelton 622-7676
Outstanding Inspections
Case Number: T11FR00900
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2011 | VIOL - ADMINISTRATION | MPURSLEY | Correction Required | 102.4 Application of building code. The design and construction of new structures shall comply with the International Building Code, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. A Certificate of Occupancy shall be provided To obtain a Certificate of Occupancy or a replacement copy, contact the city of Tucson Development services Department (DSD) located at 201 N. Stone, (520) 791-5550. |
| 04/25/2011 | VIOL - PRECAUTION AGAINST FIRE | MPURSLEY | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code. |
| 04/25/2011 | VIOL - FIRE SERVICE FEATURES | MPURSLEY | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____Maintain clearance around riser, 36" minimum |
| 04/25/2011 | VIOL - BUILDING SVCS & SYSTEMS | MPURSLEY | Correction Required | 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters. |
| 04/25/2011 | VIOL - FIRE RESIST.RATED CONST | MPURSLEY | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile |
| 04/25/2011 | VIOL - MEANS OF EGRESS | MPURSLEY | Correction Required | 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. _____Maintain minimum aisle width |
| 05/04/2011 | VIOL - HIGH PILED COMBUSTIBLES | MPursley | Correction Required | 2306.2 High Pile Storage General Fire Protection and Life Safety Requirements _____Replace sprinkler heads at 50yr. with higher temp. heads-per Dave Mann |
Completed Inspections
Case Status: COMPLETE
Case Number: T11FR00900
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2011 | COMPL - REINSPECTION | MPursley | Approved | All corrections made 5/24/11 |