Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

04/25/2011

Applicant:

DOSS LIVING TRUST

Description:

Moving Services Inc. 3/25/11 Anny/Josh Shelton 622-7676

Outstanding Inspections

Case Number: T11FR00900
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
04/25/2011 VIOL - ADMINISTRATION MPURSLEY Correction Required 102.4 Application of building code. The design and construction of new structures shall comply with the International Building Code, and any alterations, additions, changes in use or changes in structures required by this code, which are within the scope of the International Building Code, shall be made in accordance therewith. A Certificate of Occupancy shall be provided To obtain a Certificate of Occupancy or a replacement copy, contact the city of Tucson Development services Department (DSD) located at 201 N. Stone, (520) 791-5550.
04/25/2011 VIOL - PRECAUTION AGAINST FIRE MPURSLEY Correction Required 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. _____ Maintain proper ceiling clearance according to code.
04/25/2011 VIOL - FIRE SERVICE FEATURES MPURSLEY Correction Required 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____Maintain clearance around riser, 36" minimum
04/25/2011 VIOL - BUILDING SVCS & SYSTEMS MPURSLEY Correction Required 605.4.2 Power supply Relocatable power taps shall be directly connected to a permanently installed receptacle. ____Remove daisy-chained multi-plug adapters.
04/25/2011 VIOL - FIRE RESIST.RATED CONST MPURSLEY Correction Required 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire-stops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix, repair, or replace the missing fire resistive ceiling tile
04/25/2011 VIOL - MEANS OF EGRESS MPURSLEY Correction Required 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____ Fix, repair, and/or replace all exit signs in order to meet code standards 1021.2 Width. The width of exit passageways shall be determined as specified in Section 1005.1 but such width shall not be less than 44 inches (1118 mm), except that exit passageways serving an occupant load of less than 50 shall not be less than 36 inches (914 mm) in width. The required width of exit passageways shall be unobstructed. _____Maintain minimum aisle width
05/04/2011 VIOL - HIGH PILED COMBUSTIBLES MPursley Correction Required 2306.2 High Pile Storage General Fire Protection and Life Safety Requirements _____Replace sprinkler heads at 50yr. with higher temp. heads-per Dave Mann

Completed Inspections

Case Status: COMPLETE
Case Number: T11FR00900
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
05/25/2011 COMPL - REINSPECTION MPursley Approved All corrections made 5/24/11