Case: T11FR00894
Case Details
Entered Date:
04/22/2011
Applicant:
FOOD CONSPIRACY
Description:
Full Fire Prevention Inspection Building Rep: Scott Phone # 237-4602
Outstanding Inspections
Case Number: T11FR00894
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/22/2011 | INSP - FULL | JLONGO | Correction Required | Full Fire Prevention Inspection completed. Please correct the following Tucson Fire Code Violations. |
04/22/2011 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Remove the double-key lock and replace with an approved locking device such as, thumb turn lock or panic hardware (Storage Room) ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) ____________________________ (Captain) Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. |